Device, Cable, and Panel Labeling scheme.

V2 of the Device, Cable, and Panel Labeling scheme. It keeps the V1 content and makes the formats consistent. Items marked PROPOSAL are new rules that need your decision. Items marked UNTESTED have not been checked on a real printer or site.

Scope

How to name and label sites, rooms, panels, patch panels, devices, and cables in my installations. Based loosely on ANSI/TIA-606 (see "Relation to TIA-606" below). Device naming (firewalls, switches, cameras, access control) is my own convention, not part of 606.

General rules

RuleDetail
CharactersUppercase letters, digits, - and . only. No spaces, no &, no /. Lowercase is used only for the suffix letter (see below).
- (dash)Separates fields: site, then room or device, then patch panel or role. Example: SASC-IDF.1.01-P6.12
. (dot)Separates numbers inside one field: floor, door or panel number, port. Example: IDF.1.01 = IDF, floor 1, door 01. SW01.49 = switch 01, port 49.
Suffix letterLowercase a, b, ... for a second item at the same spot, or the legs of a split cable. Example: SASC-IDF.1.01b, P6.12a.
PaddingPROPOSAL. Floor: 1 character. Door, panel, device number, port: 2 digits (01). Cable serial numbers: 3 digits (001).
FloorsPROPOSAL. 1 = ground or entry floor, 2, 3 ... above. B = basement (B, then C for a second basement level).
Site prefixRequired on room, panel, and device labels. May be left off cable labels when both ends are in the same site (saves label space).
Same label both endsEvery cable gets the same label at both ends. A cable label must use the exact device and port names on this page.

Site codes

PROPOSAL: 3 or 4 uppercase letters. Fill in the table as sites are added.

CodeSiteNotes
SASC(fill in)
MHFWilson (fill in)
925(fill in)Numeric. Keep, or rename to letters? See Open questions.

Rooms, panels, and doors

Doors and panels are numbered clockwise, starting at the Main Entry. PROPOSAL: on other floors, start at the stair or elevator nearest the Main Entry.

TypeFormatExampleSecond one
Main Point of Entry (MPOE)SITE-MPOE.floor.doorSASC-MPOE.1.06N/A. One MPOE per site.
Intermediate Distribution Frame (IDF)SITE-IDF.floor.doorSASC-IDF.1.01SASC-IDF.1.01b (second IDF behind the same door)
Media cabinet / panelSITE-PNL.floor.numberSASC-PNL.2.01SASC-PNL.2.02
Facility doorSITE-DR.floor.doorSASC-DR.1.01SASC-DR.1.02
Patch panel (inside a room or cabinet)P + number, top to bottomP6P7
Patch panel portP#.portP6.12P6.12a, P6.12b (split cable)
Port, full nameSITE-ROOM-P#.portSASC-IDF.1.01-P6.12

The patch panel face only needs the short form (P6.12), because the room is already known. Use the full name in records and on riser cables.

Notes

MPOE: where the carrier's service enters the building (the demarc). In houses it is often under the stairs or in the basement. In large buildings, riser cables run from the MPOE (or the main equipment room) up to the IDFs on other floors.

IDF: the room or rack on each floor that holds the switches for that floor. It connects back to the MPOE with riser cables.

Device labels

Network and server devices
TypeFormatExampleSecond one
ISP handoff (modem / ONT)SITE-ISP##MHF-ISP01MHF-ISP02. Put the carrier name (e.g. ATT) in the records, not the label.
Firewall / routerSITE-FW##SASC-FW01SASC-FW02 (HA pair: 01 = primary)
Aggregation / distribution switchSITE-AGG##SASC-AGG01SASC-AGG02
Access switchSITE-SW##SASC-SW01SASC-SW02
Wireless access pointSITE-AP##SASC-AP01PROPOSAL (new in V2)
Server / hostSITE-SRV##SASC-SRV01PROPOSAL (new in V2)
NASSITE-NAS##SASC-NAS01PROPOSAL (new in V2)
UPS / PDUSITE-UPS##, SITE-PDU##SASC-UPS01PROPOSAL (new in V2)
Cameras
TypeFormatExampleSecond one
Internal cameraSITE-INT-WhatSASC-INT-CashRegSASC-INT-CashReg02
External cameraSITE-EXT-WhatSASC-EXT-DrivewayNSASC-EXT-DrivewayS

Cameras are named for what they look at. INT and EXT show access level at a glance: tenants and employees can usually see external cameras, but access to internal cameras is tightly controlled. The camera name is the exception to the uppercase rule, so it stays readable.

Access control (physical hardware in panels or on walls)
TypeFormatExampleSecond one
Door access hubSITE-CTL.floor.doorSASC-CTL.1.05SASC-CTL.1.05b
Reader-Flex (no hub)SITE-CTL.floor.doorSASC-CTL.1.01SASC-CTL.1.01b
Badge reader(controller)-RDRSASC-CTL.1.05-RDRSASC-CTL.1.05-RDRb (second reader, e.g. exit side)
Door intercom(controller)-INTSASC-CTL.1.05-INT

The door number in a CTL label is the same as in the door's own label (SASC-DR.1.05 uses SASC-CTL.1.05).

Cable labels

Two-line wrap label, the same at both ends:

  • Line 1 (top) = upstream end: the end closer to the ISP / core.
  • Line 2 (bottom) = downstream end: the end closer to the user or device.
  • Each line = device or port name from this page, plus .port.

The diagram above is from V1 and may still show V1 formats.

This is constantlydifferent changingfrom asTIA-606, where the near end is printed first so the order flips at each end. Here the order is always upstream first, so the label reads the same everywhere.

CableLine 1 (upstream)Line 2 (downstream)Notes
ISP to firewallISP01FW01.WAN1Second WAN: ISP02 / FW01.WAN2
Firewall to aggregation switchFW01.03AGG01.01HA: FW02.03 / AGG02.01
Aggregation to access switchAGG01.10SW01.49Bond / LAG: label each member normally (e.g. AGG02.12 / SW01.49 and AGG02.13 / SW01.50). Record the LAG in the docs.
Switch to patch panel (patch cord in rack)SW01.12P6.12
Patch panel to wall outlet (horizontal)IDF.1.01-P6.12Outlet faceplate shows the same IDSplit cable: P6.12a, P6.12b
Riser / backbone (between MPOE, IDFs, panels)MPOE.1.06-P1.01IDF.2.01-P1.01Add the site prefix if the cable leaves the site.
CameraIDF.1.01-P3.05 or SW01.05INT-CashRegThe bottom line is the camera name.
Access hub to badge readerCTL.1.05CTL.1.05-RDRIntercom: CTL.1.05 / CTL.1.05-INT
Switch to access hub / Reader-FlexSW01.20CTL.1.05

UNTESTED: I tryhave not checked how many characters fit per line on the 1.5" x 1.0" wrap label (M7-31-427). MPOE.1.06-P1.01 is 15 characters. Print a test label before committing to documentthe andriser standardize what I do in my installations.format.

Service type (from V1)

V1 used a service prefix on patch cables: NET-001, TEL-001, COM-001. In V2 the panel port ID replaces the serial number. PROPOSAL: show the service with cable color (see Relation to TIA-606) or with a third line on the label. See Open questions.

Hardware and Labels used:

labels

Printer: Brady M710 Label Maker:

BradyM710.jpg

Labels:

Label typeSizeBrady part numberPer rollPrice (V1, date unknown)Ribbon
Label TypeLabel SizeBrady Part Numer [URL]Count Per RollEstimate PriceRequired Ribbon
Basic Stickersticker1.0" x 1.0"M7-19-423250$43.50(fill
in)
Metallic Labellabel1.0" x 2.0"

M7-20-435

100$40.00(fill
in)
Cable Wrapwrap Sticker(self-laminating)1.5" x 1.0"

M7-31-427

250$68.00R4300 - ($73.0000)

Printable

Brady M710

Templates

Site Templatetemplate Guide:

Editable Document:(editable): NetworkIdentification.docx

image.pngSite template preview

Panels

Patch /bay Doorslabel Labels:templates:

PatchBaySize_12portLevitonKeystone.docx

AllPatchBaySize_12portSurfacemount.docx
panelsPatchBaySize_24portKeystone.docx
arePatchBaySize_24port.docx
counted clockwise from either MPOE or Main Entry.PatchBaySize_48port.docx

StartThese attemplates were made for V1 formats and may need updating.

Relation to TIA-606

ANSI/TIA-606 is the MainUS Doorwaycabling andadministration countstandard. clockwiseISO/IEC around14763-2 is the Facility.

international equivalent. This scheme borrows its ideas (unique IDs, both ends labeled, records kept) but uses its own formats.

This schemeTIA-606 term
MPOEEntrance Location/Typefacility (demarc). Often in the same room as the equipment room / main cross-connect (MDF).FirstExampleExpansion
IDFTelecommunications Mainroom Point of Entry(TR)(Site)-MPOE.(Floor).(door)SASC-MPO.1.6N/A - Only 1 MPOE per side
Riser cableIntermediateBackbone Distribution Framecable(Site)-IDF.(Floor).(Door)SASC-IDF.1.1IDF-1-1a, IDF-1-1b
Patch panel to outletMediaHorizontal Cabinets/Panelslink(Site)-PNL.(Floor).(Panel Number)SASC-PNL.1.1, SASC-PNL.2.1
Multi-site with site codesFacilityClass Doors:3 (campus) / Class 4 (multi-site)(Site)-FL-DR## 
SASC-01-DR01

Notes:

606

color

MPOEcodes -(from Thismemory, isnot wherechecked against the internetcurrent comesrevision)

intothebuilding.buildings,a utility hidden under stairs or in basements.  In large commercial buildings, it's widely known that risers [cables that link IDFs in other floors or wings] are used.  

IDF - This is where your switching or server

toeach

Labels:
ColorUse
OrangeDemarc In/ residentialcarrier
GreenNetwork itconnections is(customer commonlyside seenof asdemarc)
PurpleCommon equipment is(servers, locatedPBX)
WhiteFirst-level supportbackbone
GraySecond-level floor.backbone
BlueHorizontal This commonly hosts switches that connect back (to the MPOEoutlet)
BrownBetween

Cablebuildings

YellowMiscellaneous
(security, alarms)
RedKey telephone systems
606-B Notes:cable example (kept from V1)

Near end = AG09-35:01/AJ06-35:01

,

Farfar end = AJ06-35:01/AG09-35:01

.

If standing at rack location AG09, reading this near-end cable identifier will describe both the near-end and far-end locations.

AG09 = Rack or cabinetrack at grid locationAG09, AG09 within the data center

-35 = Patchpatch panel located 35 rack units from the bottombottom, :01 = port 1, / = separates near end from far end. Newer revisions (606-C, 606-D) exist. I have not checked what changed.

Changes from V1

:01

ItemV1V2
MPOESASC-MPO.1.6SASC-MPOE.1.06
IDF second unitIDF-1-1aSASC-IDF.1.01b
DoorsSASC-01-DR01SASC-DR.1.01
Firewall on cablesFW-Primary-WAN1FW01.WAN1 (same name as the device label)
Aggregation switchAGG-## and AGGR-##AGG##, with its own device row
Site 925 devices925-FW01Same format, but see Open questions about the code
Wilson-MHF patch portMHF-IDF2.1-P1.1MHF-IDF.2.01-P1.01 (same rule as every site)
Access hub suffix1.1A / 1.05a mixedAlways lowercase: 1.05b
Intercom / reader-IntCom, -Reader-INT, -RDR
CamerasINTERNAL-CashRegSASC-INT-CashReg
Camera cableSASC-CAM-1.05Port ID / camera name
Wire label orderTwo conflicting wordingsLine 1 = upstream, line 2 = downstream
Bond cables-BONDa / -BONDbLabel each member normally. LAG in rackthe AG09

records.
NewGeneral =rules, Portsite 01code intable, AP / SRV / NAS / UPS / PDU, patch panel locatednaming, 35606 rack units from the bottom of rack AG09

/ = Separator for near-end/far-end location description

AJ06 = Rack or cabinet at grid location AJ06 within the data center

-35 = Patch panel located 35 rack units from the bottom in rack AJ06

:01 = Port 01 in patch panel located 35 rack units from the bottom of the rack in AJ06

Examples mappingFirstExampleExpansion
SASC Patch Bay to Environment(Panel Number).(Port Number on Panel)P6.12P6.12a | P6.12b [only applies to split cables]
SASC to Device(Panel Number).(Port Number on Panel)P6.12P6.12a | P6.12b [only applies to split cables]
Wilson-MHF(site)-(IDF#)-(Panel Number).Port NumberMHF-IDF2.1-P1.1N/A

Device Labels:

Controllers: Physical hardware in Panels, Walls or mounted to walls

Location/TypeFirstExampleExpansion
Door Access Hub(site)-CTL.(floor)-(door number)SASC-CTL.1.05SASC-CTL.1.05a
Door Intercom(Acesss Hub)-IntComSASC-CTL.1.05-IntComIntCom
Door Badge Reader(Acesss Hub)-ReaderSASC-CTL.1.05-Reader

NetworkOpen Devices:questions

  • Fill
  • inthesitecodetable.Should925stay
    Location/Type First Example Expansion
    Firewall/Router (site)-FW##925-FW01925-FW02
    Switches(site)-SW##925-SW01925-SW02
    Cameras(location)-(object-in-camera)INTERNAL-CashRegINTERNAL-CashReg02








    Notes:

    Cameras have special naming schemes.  We define them as internalnumeric, or externalget toa quicklyletter identifycode? access.

  • Agree with Tenantsthe separator, padding, and Employeesfloor typicallyproposals?
  • can
  • Line access1 external= cameras, but internal camera accessupstream: is heavilythis policed.the order Ayou cameraactually overlookinguse in the field?
  • Service type: drop NET/TEL/COM, use cable color, or add a driveway would be called "EXTERNAL-Driveway-North"

    Patch Bay printedthird label templates:

    PatchBaySize_12portLevitonKeystone.docx
    PatchBaySize_12portSurfacemount.docx
    PatchBaySize_24portKeystone.docx
    PatchBaySize_48port.docx
    PatchBaySize_24port.docx

    Wire In between Devices:

    2x Layer labels.  Order of spanning tree.  Top of label = First location.   The bottom of the Label = end of the cable. 

  • Are
  • same youryouneedanMDFroomunits,beadded)
    DeviceFireExampleExpansion/Options
    Device

    Top: Where it terminates

    Bottom:line? What itdid terminatesCOM

    mean?



    ISP to Firewall/Router

    (site)-ISP.## [Number or name]

    FW-Primary-PORT

    MHF-ISP.001

    FW-Primary-WAN1

    ISP-AT&T

    FW-Secondary-WAN2

    Router to Distribution Switch

    FW/ROUT.Port

    AGGR-##.PORT

    FW-Primary.03

    AGGR-01.01

    FW-Secondary.03

    AGGR-02.01

    Router/Agg to L3/2 Switch IN MPOE

    AGG-##.Port

    SW##.Port

    AGGR-01.10

    SW01.49

    AGGR-02.12-BONDa

    AGGR-02.13-BONDb

    Patch Cables between IDF/MPOE and MDF always the environment

    (thing)-(floor)-(number)

    Service*-###

    *NET | *TEL | *COM |

    MHF-IDF.1.2

    NET-001

    *TEL-001

    IDF-1-2

    NET-001a

    Riser Cables

    [between MPOE, IDF, Panels]

    (site)-(thing).(floor).(number)
    (site)-(thing).(floor).(number)

    MHF-IDF.1.001

    SASC-PNL.2.001

    IDF-1-1.001a, IDF-1-1.001b

    PNL-1-2.002a

    Badge Readers

    (site)-CTL.(floor).(number)-Reader

    SASC-CTL.1.05-Reader
    Camera Cable(thing)-(floor)-(number)
    CAM-###

    SASC-CAM-1.05


    Access-Hub (notroom in panel) sites,

    (site)-CTL.(floor)-(dooror number)

    do
    SASC-CTL.1.1A SASC-CTL.1.1B
    Reader-Flextype?
  • Do you want rack positions (norack Hub)
  • as

    in 606) in the labels, or is P# top to bottom enough?

  • Print a test wrap label to check line length (site)-CTL.see UNTESTED note).
  • Ribbon part numbers for the basic and metallic labels.
    • V1 of this page, saved as a copy ending in "_old" (floor)-(doorlink number)

      to
    SASC-CTL.1.1A SASC-CTL.1.1B