Device, Cable, and Panel Labeling scheme_old ---- This is constantly changing as I try to document and standardize what I do in my installations. Hardware and Labels used: Printer: Brady M710 Label Maker: Labels: Label Type Label Size Brady Part Numer [URL] Count Per Roll Estimate Price Required Ribbon Basic Sticker 1.0" x 1.0" M7-19-423 250 $43.50 Metallic Label 1.0" x 2.0" M7-20-435 100 $40.00 Cable Wrap Sticker 1.5" x 1.0" M7-31-427 250 $68.00 R4300 - $73.00 Printable Site Template Guide: Editable Document: NetworkIdentification.docx Panels / Doors Labels:  All panels are counted clockwise from either MPOE or Main Entry. Start at the Main Doorway and count clockwise around the Facility. Location/Type First Example Expansion Main Point of Entry (Site)-MPOE.(Floor).(door) SASC-MPO.1.6 N/A - Only 1 MPOE per side Intermediate Distribution Frame (Site)-IDF.(Floor).(Door) SASC-IDF.1.1 IDF-1-1a, IDF-1-1b Media Cabinets/Panels (Site)-PNL.(Floor).(Panel Number) SASC-PNL.1.1, SASC-PNL.2.1 Facility Doors: (Site)-FL-DR##  SASC-01-DR01 Notes:  MPOE - This is where the internet comes into the building.  In residential buildings, it is commonly seen as a utility hidden under stairs or in basements.  In large commercial buildings, it's widely known that risers [cables that link IDFs in other floors or wings] are used. IDF - This is where your switching or server equipment is located to support each floor.  This commonly hosts switches that connect back to the MPOE  Cable Labels: 606-B Notes: Near end = AG09-35:01/AJ06-35:01 Far end = AJ06-35:01/AG09-35:01 If standing at rack location AG09, reading this near-end cable identifier will describe both the near-end and far-end locations. AG09 = Rack or cabinet at grid location AG09 within the data center -35 = Patch panel located 35 rack units from the bottom in rack AG09 :01 = Port 01 in patch panel located 35 rack units from the bottom of rack AG09 / = Separator for near-end/far-end location description AJ06 = Rack or cabinet at grid location AJ06 within the data center -35 = Patch panel located 35 rack units from the bottom in rack AJ06 :01 = Port 01 in patch panel located 35 rack units from the bottom of the rack in AJ06 Examples  First Example Expansion SASC Patch Bay to Environment (Panel Number).(Port Number on Panel) P6.12 P6.12a | P6.12b [only applies to split cables] SASC to Device (Panel Number).(Port Number on Panel) P6.12 P6.12a | P6.12b [only applies to split cables] Wilson-MHF (site)-(IDF#)-(Panel Number).Port Number MHF-IDF2.1-P1.1 N/A Device Labels: Controllers: Physical hardware in Panels, Walls or mounted to walls Location/Type First Example Expansion Door Access Hub (site)-CTL.(floor)-(door number) SASC-CTL.1.05 SASC-CTL.1.05a Door Intercom (Acesss Hub)-IntCom SASC-CTL.1.05-IntCom IntCom Door Badge Reader (Acesss Hub)-Reader SASC-CTL.1.05-Reader Network Devices: Location/Type First Example Expansion Firewall/Router (site)-FW## 925-FW01 925-FW02 Switches (site)-SW## 925-SW01 925-SW02 Cameras (location)-(object-in-camera) INTERNAL-CashReg INTERNAL-CashReg02 Notes: Cameras have special naming schemes.  We define them as internal or external to quickly identify access.  Tenants and Employees typically can access external cameras, but internal camera access is heavily policed.   A camera overlooking a driveway would be called "EXTERNAL-Driveway-North" Patch Bay printed label templates: PatchBaySize_12portLevitonKeystone.docx PatchBaySize_12portSurfacemount.docx PatchBaySize_24portKeystone.docx PatchBaySize_48port.docx PatchBaySize_24port.docx Wire In between Devices: 2x Layer labels.  Order of spanning tree.  Top of label = First location.   The bottom of the Label = end of the cable.  Device Fire Example Expansion/Options Device Top: Where it terminates Bottom: What it terminates  ISP to Firewall/Router (site)-ISP.## [Number or name] FW-Primary-PORT MHF-ISP.001 FW-Primary-WAN1 ISP-AT&T FW-Secondary-WAN2 Router to Distribution Switch FW/ROUT.Port AGGR-##.PORT FW-Primary.03 AGGR-01.01 FW-Secondary.03 AGGR-02.01 Router/Agg to L3/2 Switch IN MPOE AGG-##.Port SW##.Port AGGR-01.10 SW01.49 AGGR-02.12-BONDa AGGR-02.13-BONDb Patch Cables between IDF/MPOE and the environment (thing)-(floor)-(number) Service*-### *NET | *TEL | *COM | MHF-IDF.1.2 NET-001 *TEL-001 IDF-1-2 NET-001a Riser Cables [between MPOE, IDF, Panels] (site)-(thing).(floor).(number) (site)-(thing).(floor).(number) MHF-IDF.1.001 SASC-PNL.2.001 IDF-1-1.001a, IDF-1-1.001b PNL-1-2.002a Badge Readers (site)-CTL.(floor).(number)-Reader SASC-CTL.1.05-Reader Camera Cable (thing)-(floor)-(number) CAM-### SASC-CAM-1.05 Access-Hub (not in panel) (site)-CTL.(floor)-(door number) SASC-CTL.1.1A SASC-CTL.1.1B Reader-Flex (no Hub) (site)-CTL.(floor)-(door number) SASC-CTL.1.1A SASC-CTL.1.1B